Hi,
I have an EMS-4 and wired sensors in GPIO
#1 oilpress
#2 oiltemp
#3 FuelPress
#4 FuelLevel
#5 VVT
#7 Boos solenoid
AEMNet connected AQ1 and AEMnet Conected CD7
how do i get this sensors to show in the CD7 and make sure they log in the AQ1
when i try to configure the CD7 the Inputs does not show all the PGIO
only 2, 4, 5, 6, 7 but i need 1, 3?
also some how does not looks like is sending the correct value
help please
Hey Jose,
We just made a new dbc for you, please load this into the cd-7 using the dash design software and make the following changes to your calibration file in AEM tuner . These changes will allow GPIO 1 and 3 to show up on the CD-7. All of the GPIO channels will show up in the dash as 0-5v, from there you will be able to create a new output to rescale the 0-5v signal into something like oil pressure or fuel level.
AEM 30-6905 EMS-4 SI_GPIO1_GPIO3.dbc
Thank you, good help, now the sreen show allot of numbers on the oilpress for example
i used the sensor AEMconversion but does not seams to work
you have an idea why ?
also this data now go to my AQ1 but i dont know what chanel is what
AQ1 show ADCR08, 11, 13, 14, 15, 16, 17, 18 ?
it is possible to get the GPS data from the AQ1 with GPS serial setup in to the CD7 ?
ADCR08 = ECU Battery Volts
ADCR11 = GPIO2 Voltage
ADCR13 = GPIO4 Voltage
ADCR14 = GPIO5 Voltage
ADCR15 = GPIO6 Voltage
ADCR16= GPIO7 Voltage
ADCR17= GPIO1 Voltage
ADCR18= GPIO3 Voltage
there is 2 GPIO 2 in your list, and no 3 :(
Fixed above